Worcester CDi Combi N.G Service Booklet page 39

Floor mounted and wall hung rsf gas fired condensing boilers
Table of Contents

Advertisement

d6
and fault indicator LED are flashing. (Boiler not available for demands)
Tank overheat thermostat defective
Check
1.
B Power OFF the appliance.
B Disconnect the boiler mains
connection.
Check if thermostat is connected
on PCB via ST9
2.
B Disconnect lead on thermostat.
Measure the thermostat for
continuity.
Is there continuity?
3.
B unplug connector ST9.
Test harness for continuity.
Is there continuity?
4.
The PCB control board is damaged.
Tab. 22 d6 Error codes
8 716 115 748 (2009/09)
Supplied By www.heating spares.co Tel. 0161 620 6677
Action
yes
go to 2
no
B Ensure that ST9 is plugged onto the PCB.
B Reconnect the boiler electrical mains.
B Power ON the appliance
d6? go to 4
yes
B Reconnect lead on thermostat.
go to 3
no
B Change thermostat.
B Reconnect lead on thermostat.
B Reconnect the boiler electrical mains
connection.
B Power ON the appliance
d6? go to 4
yes
d6? go to 4
no
B Change or fix wiring to thermostat.
B Reconnect the boiler electrical mains
connection.
B Power ON the appliance.
d6? go to 4
B Reconnect the boiler electrical mains
connection.
B Power ON the appliance.
B Make a note of the altered service function
settings.
B Power OFF the appliance.
B Disconnect the boiler electrical connection.
B Change the control board PCB.
B Reconnect the boiler electrical connection.
B Turn ON the appliance.
B Restore service settings previously noted.
RECTIFYING FAULTS