Electrical Requirements - Jenn-Air 36" Installation Instructions And User Manual

(91,4 cm) wall-mount canopy range hood
Table of Contents

Advertisement

Available languages

Available languages

For Non-Vented
(recirculating)
Installations
If it is not possible to vent cooking fumes and vapors to the
outside, the hood can be used in the non-vented (recirculating)
version, fitting a charcoal filter and the deflector. Fumes and
vapors are recycled through the upper chimney cover louvers.
To order the charcoal filter and recirculation
kit, see
"Accessories"
in the "Assistance and Service" section.
Roof Venting
Wall Venting
Non-vented
(recirculating)
A. Roof cap
A. Wall cap
A. Deflector
B. 6" (15.2 cm)
B. 6" (15.2 cm)
B. 6" (15.2 cm)
round vent
round vent
round vent
Calculating Vent System Length
To calculate the length of the system you need, add the
equivalent feet (meters) for each vent piece used in the system.
Vent Piece
6" (15.2 cm) Round
45 ° elbow
2.5 ft
(0.8 m)
Example
vent system
90°elbow
I_
6 t't(1.8m)_l
..... Wall cap
The following example
falls within the maximum
recommended
vent length of 35 ft (10.7 m).
1 - 90 ° elbow
1 - wall cap
8 ft (2.4 m) straight
Length of system
= 5.0 ft (1.5 m)
= 0.0 ft (0.0 m)
= 8.0 ft (2.4 m)
= 13.0 ft (3.9 m)
Observe all governing codes and ordinances.
Ensure that the electrical installation is adequate and in
conformance
with National Electrical Code, ANSI/NFPA 70 (latest
edition), or CSA Standards C22.1-94, Canadian Electrical Code,
Part 1 and C22.2 No. 0-M91 (latest edition) and all local codes
and ordinances.
If codes permit and a separate ground wire is used, it is
recommended
that a qualified electrician determine that the
ground path is adequate.
A copy of the above code standards can be obtained from:
National Fire Protection Association
1 Batterymarch
Park
Quincy, MA 02169-7471
CSA International
8501 East Pleasant Valley Road
Cleveland, OH 44131-5575
A 120 volt, 60 Hz., AC only, 15-amp, fused electrical circuit is
required.
90 ° elbow
5.0 ft
(1.5 m)
Maximum equivalent vent length is 35 ft (10.7 m).