Cabinet Dimensions
10" (25.4 cm) rain.
13" (33.0
max.
2" (5.1 cm) rain.
)" (22.9 cm) rain.*
Vent and power
_ly came
, location
Side
cabinet
"X"
bottom
of
I
canopy
to cooking
I
SILll'faoe
)Centerline
surface
*For non-vented (recirculating)
installations
IMPORTANT:
Minimum distance "X": 24" (61.0 cm) from electric cooking
surface.
Minimum distance "X": 30" (76.2 cm) from gas cooking
surface.
Suggested maximum distance "X": 36" (91.4 cm)
NOTE: For best performance of the Auto Sense feature, the
range hood should be installed at 24" (61.0 cm) from an electric
cooking surface and 30" (76.2 cm) from a gas cooking surface.
The chimneys can be adjusted for different ceiling heights. See
the following chart.
Vented Installations
Min. ceiling height
Max. ceiling height
Electric cooking
7' 10" (2.39 m)
10' 4" (3.24 m)
surface
Gas cooking
8' 4" (2.54 m)
10' 4" (3.24 m)
surface
Non-vented (recirculating)
Installations
Min. ceiling height
Max. ceiling height
Electric cooking
7' 10" (2.39 m)
10' 4" (3.24 m)
surface
Gas cooking
8' 4" (2.54 m)
10' 4" (3.24 m)
surface
*NOTE: The range hood chimneys are adjustable and designed
to meet varying ceiling or soffit heights depending on the
distance "X" between the bottom of the range hood and the
cooking surface. For higher ceilings from 10' 4" to 12' (3.24 m to
3.66 m), a Stainless Steel Chimney Extension Kit Part Number
W10646864
is available from your dealer or an authorized parts
distributor. The chimney extension replaces the upper chimney
shipped with the range hood.
(_ye_ste_I
_:_e_e
s e_s_y_}
Vent system must terminate to the outdoors, except for non-
vented (recirculating)installations.
Do not terminate the vent system in an attic or other enclosed
area.
Do not use 4" (10.2 cm) laundry-type wall cap.
Use metal vent only. Rigid metal vent is recommended.
Plastic or metal foil vent is not recommended.
The length of vent system and number of elbows should be
kept to a minimum to provide efficient performance.
For the most efficient and quiet operation:
Use no more than three 90 ° elbows.
Make sure there is a minimum of 24" (61.0 cm) of straight
vent between the elbows if more than 1 elbow is used.
Do not install 2 elbows together.
Use clamps to seal all joints in the vent system.
The vent system must have a damper. If the roof or wall cap
has a damper, do not use the damper supplied with the range
hood.
Use caulking to seal exterior wall or roof opening around the
cap.
The size of the vent should be uniform.
Cold Weather
Installations
An additional back draft damper should be installed to minimize
backward cold air flow and a thermal break should be installed to
minimize conduction
of outside temperatures
as part of the vent
system. The damper should be on the cold air side of the thermal
break.
The break should be as close as possible to where the vent
system enters the heated portion of the house.
Makeup
Air
Local building codes may require the use of makeup air systems
when using ventilation systems greater than specified CFM of air
movement. The specified CFM varies from locale to locale.
Consult your HVAC professional for specific requirements in your
area.
Venting Methods
This canopy hood is factory set for venting through the roof or
wall.
A 6" (15.2 cm) round vent system is needed for installation (not
included). The hood exhaust opening is 6" (15.2 cm) round.
A 6" to 8" (15.2 cm to 20.3 cm) vent adapter is available for 8"
(20.3 cm) vent systems. See the "Assistance
or Service" section
to order.
Vent system can terminate either through the roof or wall. To vent
through a wall, a 90 ° elbow is needed.
Rear discharge
A 90° elbow may be installed immediately above the hood.