8 Communication

This chapter describes the communication features of the Eaton 9395 450–550 kVA UPS and provides
information about connecting hardware and using Terminal mode. For location of the customer
interface panels and terminals, see Figure 4-4 on page 29 and Figure 4-11 on page 36 through Figure 4-
13 on page 37.

8.1 X-Slot cards

The Eaton 9395 UPS has four X-Slot communication bays (see Figure 4-11 on page 36 for bay
locations). The UPS is compatible with the following X-Slot cards (see Figure 8-1):
Modbus card - provides direct integration of UPS information (meters and status) to a Building
Management System (BMS) using the Modbus RTU protocol.
ConnectUPS-X Web/SNMP card - provides remote monitoring through a Web browser interface, e-
mail, and a network management system (NMS) using SNMP; connects to a twisted-pair Ethernet
(10/100BaseT) network. It has a built-in switching hub that allows three additional network devices
to be connected to the network without the requirement of additional network drops. This card is
provided as standard equipment with the UPS.
NOTE
The Modem card cannot be installed in X-Slot 2.
Modem card - provides "out-of-band" remote notification and monitoring using modem
communication directly to cell phones and pagers.
Relay Interface card (AS/400) - has isolated dry contact (Form-C) relay outputs for UPS status:
Utility failure, Low battery, UPS alarm/OK, or On bypass when interfacing with IBM® AS/400
computers, other relay connected computers, and industrial applications.
Industrial Relay card (IRC) - indicates the operating status of the UPS system using the customer's
monitoring equipment. The IRC uses four isolated normally-open or normally-closed dry relay
contacts to indicate the UPS status. Normal, Bypass, Battery, and Alarm modes can be monitored.

Figure 8-1. Optional X-Slot cards

8.2 LanSafe Power Management Software

Each Eaton 9395 UPS ships with LanSafe® Power Management Software. To begin installing LanSafe
software, see the instructions accompanying the Software Suite CD.
1027574
Revision E
UPS 450-550 kVA (2x225 - 2x275 kVA)
User's and Installation Guide
119