Mains Supply - ESAB Warrior 500i CC/CV Instruction Manual

Hide thumbs Also See for Warrior 500i CC/CV:
Table of Contents

Advertisement

Available languages

Available languages

  • ENGLISH, page 1
5 INSTALLATION
5.4

Mains supply

NOTE!
Mains supply requirements
High power equipment, due to the primary current drawn from the mains supply,
may influence the power quality of the grid. Therefore, connection restrictions or
requirements regarding the maximum permissible mains impedance, or the
required minimum supply capacity at the interface point to the public grid, may
apply for some types of equipment (see technical data). In this case, it is the
responsibility of the installer or user of the equipment to ensure, in consultation
with the distribution network operator if necessary, that the equipment may be
connected.
Make sure that the welding power source is connected to the correct supply voltage and that
it is protected by the correct fuse rating. A protective ground connection must be made in
accordance with regulations.
Table 1. Recommended fuse sizes and minimum cable area Warrior 500i CC/CV
Mains voltage
Mains cable area
Phase current I
eff
Fuse
anti-surge
type C MCB
Mains voltage
Mains cable area
Phase current I
eff
Fuse
anti-surge
type C MCB
NOTE!
The mains cable areas and fuse sizes as shown above are in accordance with
Swedish regulations. Use the power source in accordance with the relevant
national regulations.
0463 341 131
Warrior 500i CC/CV
380V 3~ 50/60 Hz
2
4C 8Awg / 4G 6mm
30A
35A
32A
Warrior 500i CC/CV
460V 3~ 50/60 Hz
2
4C 8Awg / 4G 6mm
28A
35A
32A
- 12 -
440V 3~ 50/60 Hz
2
4C 8Awg / 4G 6mm
28A
35A
32A
575V 3~ 50/60 Hz
2
4C 8Awg / 4G 6mm
24A
25A
25A
© ESAB AB 2013

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents