TABLE OF CONTENTS
EEPROM Memory .............................................................................. 2
Supervision ........................................................................................ 2
Operation ........................................................................................... 2
PC1500RK Keypad ............................................................................ 2
Mounting the Panel ............................................................................ 3
Keypad Wiring ................................................................................... 3
Fire Zone Wiring ................................................................................. 3
AC Power Wiring ................................................................................ 3
Battery Connection ............................................................................ 3
Introduction ........................................................................................ 3
Master Code ...................................................................................... 3
2nd Master Code ............................................................................... 3
Arming ................................................................................................ 3
Disarming ........................................................................................... 4
Zone Bypassing ................................................................................. 4
Trouble Conditions ............................................................................ 4
Alarm Memory .................................................................................... 4
EEPROM Reset .................................................................................. 5
Quick-Exit Command ......................................................................... 6
Quick-Arm Command ........................................................................ 6
Keypad Zones ................................................................................... 6
Introduction ........................................................................................ 6
Programming ..................................................................................... 6
Binary Data Display ........................................................................... 7
NOTES FOR UL INSTALLATIONS
This equipment is UL listed in accordance with standard UL1023
(Household Burglar - Alarm System Units), standard UL985 (Household
Fire Warning Units) and UL1635 (Digital Alarm Communicator System
Units).
This equipment has the capability of being programmed for operational
features that are not allowed for UL recognized installations. To stay
within the standard for household applications, the installer should use
the following guidelines when configuring the system.
1. ALL components of the system should be UL listed for the intended
application. Note elsewhere in this manual, recommendations for
smoke detectors and battery to be used with this equipment.
2. If this system is configured for "Fire", the installer should refer to
NFPA Standards #74 for details on locating smoke detectors. When
the "Fire" feature is enabled, there must be at least one UL recognized
indoor Fire Alarm Warning Signaling Appliance.
3. Maximum allowed entry time = 45 seconds
Maximum allowed exit time = 60 seconds
2
2
3
[17] System Times ........................................................................... 10
Entry/Exit Times ............................................................................... 10
3
PGM Terminal .................................................................................. 11
[32] 5th System Option Code .......................................................... 12
[34] 6th System Option Code .......................................................... 12
6
Minimum allowed bell cutoff time = 4 minutes
4. User bypass must be enabled so that a user code is required to
bypass zones.
5. The installer should caution the user to NOT give system information
to casual users. Eg. Codes, bypass methods, etc. to babysitters or
home service people. Only the "One-Time" use code should be
given to the casual user.
6. The installer should advise the user and note in the user manual:
• Service organization name and telephone number
• The programmed exit time
• The programmed entry time
7. Remote programming must be disabled.
8. The Master Code should be changed from the factory default setting
and the new Master Code recorded in the User Manual.
9. To achieve 24 hour battery stand-by, the combined AUX and Alarm
Load shall not exceed 90mA and 600mA respectively. A 12V 7.0Ah
sealed lead-acid battery shall be employed.