Figure 7-1 Connecting The Service Cable To A Solaris Service; To Make A Connection To The Storage Service Processor From An Onsite System - Sun Microsystems StorEdge 3900 Series Reference Manual

Hide thumbs Also See for StorEdge 3900 Series:
Table of Contents

Advertisement

To Make a Connection to the Storage Service
Processor from an Onsite System
1. Connect one end of the service cable (part number 530-2093-01) onto the Serial
Console Port of the Service Panel.
Serial Port
on Solaris
Server
FIGURE 7-1
2. Connect the other end to an available serial port on your onsite Solaris system.
Note – The DB9 (part number 530-3100-01) and DB25 (part number 530-2889-03)
adapters, shipped with each unit, are used to make this connection.
3. From the onsite system establish a connection to the Storage Service Processor.
The commands used to make the connection will vary depending on the onsite
system. For example, from a Solaris server you could type:
# tip -9600 /dev/ttyX
Connected
Once the connection is made, press Return.
To Make a Connection to the Storage Service
Processor from a Remote System
1. Establish a remote connection to the site through the Sun StorEdge Remote
Response modem.
86
Sun StorEdge 3900 and 6900 Series Reference Manual • February 2002
Service Cable
SP LAN
Connecting the Service Cable to a Solaris Service
Service Panel
Serial Console
Service Port
USB1
NTC
Enet
USB2
Modem