Thermal guidelines for mounting systems in a non-sun cabinet
Hide thumbs Also See for Fire 4810:

Advertisement

Quick Links

Thermal Guidelines for Mounting
Sun Fire™ 4810/4800/3800
Systems in a Non-Sun Cabinet
Sun Microsystems, Inc.
901 San Antonio Road
Palo Alto, CA 94303
U.S.A. 650-960-1300
Part No. 806-6073-10
August
2001, Revision A
Send comments about this document to: docfeedback@sun.com

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the Fire 4810 and is the answer not in the manual?

Questions and answers

Summary of Contents for Sun Microsystems Fire 4810

  • Page 1 Thermal Guidelines for Mounting Sun Fire™ 4810/4800/3800 Systems in a Non-Sun Cabinet Sun Microsystems, Inc. 901 San Antonio Road Palo Alto, CA 94303 U.S.A. 650-960-1300 Part No. 806-6073-10 August 2001, Revision A Send comments about this document to: docfeedback@sun.com...
  • Page 2 Sun, Sun Microsystems, the Sun logo, AnswerBook2, docs.sun.com, Sun Fire, and Solaris are trademarks, registered trademarks, or service marks of Sun Microsystems, Inc. in the U.S. and other countries. All SPARC trademarks are used under license and are trademarks or registered trademarks of SPARC International, Inc.
  • Page 3 Sun Fire 4810/4800/3800 Systems in a Non-Sun Cabinet In this book, Sun Fire™ 4810/4800/3800 are referred to as systems. Also, any enclosure into which Sun Fire 4810/4800/3800 systems would mount is referred to as cabinet. Disclaimer These guidelines are intended to assist those who would install the Sun Fire™ 4810/ 4800/3800 systems at the end users’...
  • Page 4 Conditions Any systems mounted in a rack with Sun systems must have front to back cooling (no side to side). The front of the cabinet should not be facing, nor be in the path of the exhaust air from any other systems or cabinets. It is recommended that the cabinet allow 0.188 cubic meters per second (600 cubic feet per minute) of exhaust air out of the cabinet by way of the exhaust fans located at the top of the cabinet.
  • Page 5 4800 - Front View 4800 - Rear View 3800- Front View 3800 - Rear View System Air Inlet System Air Exhaust Power Supply Air Inlet Power Supply Air Exhaust Thermal Guidelines for Mounting Sun Fire 4810/4800/3800 Systems in a Non-Sun Cabinet...
  • Page 6 4810 - Front View 4810 - Rear View System Air Exhaust System Air Inlet Power Supply Air Exhaust Power Supply Air Inlet Thermal Guidelines for Mounting Sun Fire™ 4810/4800/3800 Systems in a Non-Sun Cabinet • August 2001...
  • Page 7 Component temperatures should be below warning temperature when operating in a normal computer lab environment as described in Chapter 3.1 of the Sun Fire™ 6800/4810/4800/3800 Systems Site Planning Guide (805-7365). Thermal Guidelines for Mounting Sun Fire 4810/4800/3800 Systems in a Non-Sun Cabinet...
  • Page 8 Component temperature limits TABLE 2 Not to exceed junction temperature ° ° ASC,DX,SDC,AR ° I/O, ASIC Thermal Guidelines for Mounting Sun Fire™ 4810/4800/3800 Systems in a Non-Sun Cabinet • August 2001...