If this fi replace is not Fireplace Installation ..............10 properly installed, a Clearances ...................10 house fi re may result. Crate Removal ..................10 Locating The FP30 Fireplace ..............10 For your safety, fol- Procedure:.....................11 low the installation Dimensions .................11 Minimum Framing Dimensions..........12 instructions.
2. To refuel, adjust air control all the way to the left(High), Your PACIFIC ENERGY fi replace is designed for maximum and give the fi re time to brighten. Open the door slowly, overall efficiency at a moderate fi ring rate. Over fi ring is this will prevent back puffing.
- DO NOT CONNECT THIS UNIT TO A CHIMNEY FLUE SERVING ANOTHER APPLIANCE. The FP30 fi replace may not be installed in a factory built fi replace unless tested with the fi replace. The fi replace is not tested. - DO NOT INSTALL IN A SLEEPING ROOM.
WALL AND CEILING/ROOF MUST BE MAINTAINED. NOTE: Check local codes concerning installation requirements and restrictions in your area. NOTE: The FP30 can be installed with a minimum 15ft(4.5m) of chimney with or without offsets. NOTE: Combustible materials cannot be used in the space directly above the fi replace.
Offsets The chimney for the FP30 can be installed with a maximum FIG. #10 of four 45° elbows(in Canada) and four 30° elbows(in U.S.A.) as shown in Fig. #10. Installation: 1. Install the fi rst elbow; turn it in the required direction. It INSTALL SUPPORTS AS PER is required to secure connections with three (3) #8 x ½"...
To draw outside combustion air, connect the cover plate on the side you do not wish to draw the air from and con- nect the outside combustion air adapter(FP30.OAIR) to the side you wish to draw air from. (Both cover plate and adpater provided) (Fig.
2” 51mm Floor Blower Wiring 18" [457mm] The FP30 must be connected 120 VAC household electrical 8" [203mm] 8" [203mm] system. Non-combustible fl oor protector It is recommended to also connect the unit to a wall switch or fan speed controller.(1.1 amp load or greater)
Facing and Air Inlet Cement Board Installation FIG. #20 The front facing area of the FP30 must be covered with non- combustible cement board as shown in Fig.#20 and #21 prior to applying any fi nishing material. The cement board can be attached to the framing and to the front of the unit outside of the dimensioned area shown by the dotted line in Fig.#20.
• BLOWER ELECTRICAL RATING 115V, 60HZ, 1.1AMP • REPLACE GLASS ONLY WITH 5mm CERAMIC GLASS. • DO NOT USE OR INSTALL COMPONENTS OR PRODUCTS NOT SPECIFIED IN PACIFIC ENERGY INSTALLATION INSTRUCTIONS. • DO NOT USE A FIREPLACE INSERT OR OTHER PRODUCTS NOT SPECIFIED FOR USE WITH THIS PRODUCT.