IMPORTANT:
THESE INSTRUCTIONS ARE TO
REMAIN WITH THE HOMEOWNER.
PLEASE SAVE THESE INSTRUCTIONS.

SAFETY NOTICE

If this fireplace is not properly installed, a
house fire may result. For your safety, follow
the installation instructions. Contact local
building or fire officials about restrictions
and installation inspection requirements in
your area.
TESTED and LISTED to CAN/ULC
S610-M87 AND UL 127
Meets the Environmental Protection Agency's
May 2015 Particulate Emission Standards
©PACIFIC ENERGY FIREPLACE
120216-32
PRODUCTS LTD. - 2014
INSTALLATION
AND OPERATING
INSTRUCTIONS
MODEL: FP30, FP30AR
SERIES: B
ZERO CLEARANCE WOOD
FIREPLACE
FP30, FP30AR
SERIAL #
5055.5152

Advertisement

Table of Contents
loading

Summary of Contents for Pacific energy FP30

  • Page 1: Safety Notice

    INSTALLATION AND OPERATING INSTRUCTIONS TESTED and LISTED to CAN/ULC S610-M87 AND UL 127 Meets the Environmental Protection Agency's May 2015 Particulate Emission Standards MODEL: FP30, FP30AR SERIES: B ZERO CLEARANCE WOOD FIREPLACE ©PACIFIC ENERGY FIREPLACE 120216-32 FP30, FP30AR 5055.5152...
  • Page 2: Table Of Contents

    Label ....................31 PLEASE SAVE THESE INSTRUCTIONS This manual describes the installation and operation of the Pacific Energy, FP30 wood heater. This heater meets the 2015 U.S. Environmental Protection Agency's crib wood emission limits for wood heaters sold after May 15, 2015.
  • Page 3: Safety And Maintenance

    Safety and 6. DOOR GASKETS - The gasket used by Pacific Energy (7/8"(22mm) medium density fibreglass rope) requires Maintenance only light pressure to seal. This will prolong seal life. It is important that the door seal be maintained in good condi- tion.
  • Page 4: Maintenance Checks

    If necessary, replace with gasket #SUMB.31396 - Boost manifold cover. available from your Pacific Energy dealer. Re-install baffle assembly in reverse order. Ensure that the two side pieces of insulation are set inside the side rails and tight against the When Cleaning the baffle.
  • Page 5: Blower Replacement

    #4). 10. Reverse the process to re-install blower. Make sure the gasket is in good condition. Replace if needed. TERMINAL GROUND WIRE BLOCK WINGNUTS FIG. #4 NUTS TO SWITCH OR SPEED CONTROLLER FP30 B 120216-32 ©PACIFIC ENERGY FIREPLACE PRODUCTS LTD.
  • Page 6: Chimney Smoke And Creosote Formation

    Contact your local municipal or provincial fire authority for further information on how to handle a chimney fire. It is most important that you have a clearly understood plan on how to handle a chimney fire. ©PACIFIC ENERGY FIREPLACE FP30 B 120216-32 PRODUCTS LTD.
  • Page 7: Operation

    1. Set air control to a desired setting. If smoke pours down across the glass (waterfall effect) this indicates you have Your PACIFIC ENERGY fireplace is designed for maximum shut the control down too soon or you are using too low overall efficiency at a moderate firing rate.
  • Page 8: Restarting After Extended Or Overnight Burns

    3. Inadequate draft may cause back puffing into the room and plugging of the chimney. Smoke leaking into the room through appliance and chimney connector joints indicates inadequate draft. ©PACIFIC ENERGY FIREPLACE FP30 B 120216-32 PRODUCTS LTD.
  • Page 9: Firebrick Installation

    9” X 3 1/2” X 1 1/4” (102 mm x 115 mm x 32 mm) 3245.501 7 1/4” X 4 1/2” X 1 1/4” (184 mm x 115 mm x 32 mm) 245.001 FP30 B 120216-32 ©PACIFIC ENERGY FIREPLACE PRODUCTS LTD.
  • Page 10: Fireplace Installation

    Under no circumstances is this heater to be installed in a makeshift or "temporary" manner. It may be fired only The FP30 fireplace may not be installed in a factory built fireplace after the installation conditions have been met. unless tested with the fireplace. The fireplace is not tested.
  • Page 11: Dimensions

    27 1/2" FIG. #6 [699mm] FP30 & 30 3/4" FP30AR [781mm] 23" [584mm] 47" [1.19m] 30 1/8" 34 7/8" [765mm] [886mm] 23 7/8" [606mm] 13 1/4" 9 5/8" [337mm] [245mm] 42" [1.07m] FP30 B 120216-32 ©PACIFIC ENERGY FIREPLACE PRODUCTS LTD.
  • Page 12: Minimum Framing Dimensions

    DIMENSIONS AROUND THE TO REAR WALL FIREPLACE INCLUDE THE INNER DRYWALL BOARD. 24" 610mm 16” 406mm 56" 1.42m 73" 1.85m " 641mm " 137mm 73" " 1.85m 905mm " 2.62m " 1.61m 56" 1.42m ©PACIFIC ENERGY FIREPLACE FP30 B 120216-32 PRODUCTS LTD.
  • Page 13: Framing Kit Assembly

    Using the screws provided (1), attach the framing kit legs(4) to the bottom stud (2). • Next, attach each center support(3) to the bottom stud(2) and then attach the top stud(2) to the center supports(3). FIG. #8 FP30 B 120216-32 ©PACIFIC ENERGY FIREPLACE PRODUCTS LTD.
  • Page 14 Fireplace Anchor Plate O p t i o n a l A n c h o r Plate spacer may be required with some chimney brands. Non-combustible floor protector ©PACIFIC ENERGY FIREPLACE FP30 B 120216-32 PRODUCTS LTD.
  • Page 15: Chimney Installation

    WALL AND CEILING/ROOF MUST BE MAINTAINED. NOTE: Check local codes concerning installation requirements and restrictions in your area. NOTE: The FP30 can be installed with a minimum 15ft(4.5m) of chimney with or without offsets. NOTE: Combustible materials cannot be used in the space directly above the fireplace.
  • Page 16: Offsets

    Offsets The chimney for the FP30 can be installed with a maximum FIG. #10 of four 45° elbows(in Canada) and four 30° elbows(in U.S.A.) as shown in Fig. #10. Installation: 1. Install the first elbow; turn it in the required direction. It INSTALL SUPPORTS AS PER is required to secure connections with three (3) #8 x ½"...
  • Page 17: Combustion Air

    To draw outside combustion air, connect the cover plate on the side you do not wish to draw the air from and con- nect the outside combustion air adapter(FP30.OAIR) to the side you wish to draw air from. (Both cover plate and adpater provided) (Fig.
  • Page 18: Floor Protector

    2” 51mm Floor Blower Wiring 18" [457mm] The FP30 must be connected 120 VAC household electrical 8" [203mm] 8" [203mm] system. Non-combustible floor protector It is recommended to also connect the unit to a wall switch or fan speed controller.(1.1 amp load or greater)
  • Page 19: Remote Heat Duct Installation

    If you require more than 5ft(1.5m) of the Type ”B” flexible venting order Part #5095.7. INSTALLATION: 1. Using a pair of tin snips, cut away the square section blocking the heat duct openings and cut out and remove insulation(Fig.#17). FP30 B 120216-32 ©PACIFIC ENERGY FIREPLACE PRODUCTS LTD.
  • Page 20: Electrical Wiring

    WIRED TO A SEPARATE SWITH OR SPEED CONTROL- LER THAN THE CONVECTION BLOWERS ON THE UNIT. FIG. #18 BLOWER SPEED 120 VOLTS 60 Hz CONTROL 0.7 AMPERES G (green) L1 (white) L2 (black) USE ONLY COPPER CONDCUTORS ©PACIFIC ENERGY FIREPLACE FP30 B 120216-32 PRODUCTS LTD.
  • Page 21 CHIMNEY INSTALLTIONS NOT SHOWN ROUND DUCT (6”(150mm) TYPE ”B”) MAXIMUM DUCT LENGTH 20’(6.1m). FP30 B 120216-32 ©PACIFIC ENERGY FIREPLACE PRODUCTS LTD.
  • Page 22: Facing And Air Inlet

    Facing and Air Inlet Cement Board Installation FIG. #20 The front facing area of the FP30 must be covered with non- combustible cement board as shown in Fig.#20 and #21 prior to applying any finishing material. The cement board can be attached to the framing and to the front of the unit outside of the dimensioned area shown by the dotted line in Fig.#20.
  • Page 23: Mantel Clearances

    52 1/2"(1.33m) 8"(203mm) 53"(1.35m) 18"(457mm) 9"(229mm) 53 1/2"(1.36m) 10"(254mm) 54"(1.37m) 19"(483mm) 11"(279mm) 54" 1/2”(1.38m) 12"(305mm) 55"(1.4m) 20"(508mm) Combustible Mantle (A) 12"(305mm) (A)4"(102mm) 7’(2.13m) Floor to ceiling Minimum (B) 55" 1.4m (B) 51" 1.3m FP30 B 120216-32 ©PACIFIC ENERGY FIREPLACE PRODUCTS LTD.
  • Page 24: Troubleshooting

    1. Combustion air supply blocked - Check outside air supply for obstruction - Check that room air cover is removed 2. Draft too low - Chimney plugged or restricted, inspect and clean - Chimney oversized or otherwise unsuitable, consult Dealer ©PACIFIC ENERGY FIREPLACE FP30 B 120216-32 PRODUCTS LTD.
  • Page 25: Understanding & Operating Your Pacific Energy Fireplace

    Understanding & Operating Your Pacific Energy Fireplace The Pacific Energy line of fireplaces are a culmination of OPERATING TIPS years of research and development. Designed to be efficient, clean-burning and user-friendly, this heater will give you years 1. Always use dry, seasoned firewood, up to 20" long. Load of warm service.
  • Page 26: Replacement Parts

    16 ..Upper Arch Louvre Assy..... FP30.ARLOUVRE 17 ..Arch Ash Shelf ........FP30.ARSHLF 18 ..Lower Louvre Assy....FP30.ARLLOUVRE All parts may be ordered from your nearest Pacific Energy 19 ..Door Casting, Arch ........5035.0222 dealer. Check website(pacificenergy.net) for the location of the dealer nearest you.
  • Page 27: Warranty Information

    3 Year Comprehensive Pacific Energy will replace or repair any part found to be defective (parts and labor) for three years from the date of pur- chase. This coverage includes electrical components (blowers, speed controls and thermal switches).
  • Page 28 ©PACIFIC ENERGY FIREPLACE FP30 B 120216-32 PRODUCTS LTD.
  • Page 29 FP30 B 120216-32 ©PACIFIC ENERGY FIREPLACE PRODUCTS LTD.
  • Page 30 ©PACIFIC ENERGY FIREPLACE FP30 B 120216-32 PRODUCTS LTD.
  • Page 31: Label

    • BLOWER ELECTRICAL RATING 115V, 60HZ, 1.1AMP • REPLACE GLASS ONLY WITH 5mm CERAMIC GLASS. • DO NOT USE OR INSTALL COMPONENTS OR PRODUCTS NOT SPECIFIED IN PACIFIC ENERGY INSTALLATION INSTRUCTIONS. • DO NOT USE A FIREPLACE INSERT OR OTHER PRODUCTS NOT SPECIFIED FOR USE WITH THIS PRODUCT.
  • Page 32 PACIFIC ENERGY FIREPLACE PRODUCTS LTD. 2975 Allenby Rd., Duncan, B.C. V9L 6V8 Web site: http://www.pacificenergy.net Printed in Canada ©PACIFIC ENERGY FIREPLACE PRODUCTS LTD.