NFS Supra

5.4.6 Disablement led indication with delay

The delay may turn on (EN54-2) the disablement led depending on the configuration.
Configuration of disablement led with delays:
Select the sounders configuration menu by pressing at the same time the following keys:
(KEYPAD ACCESS=ON + DELAY ON/OFF=ON).
The cyclic change of the function is made by pressing the RESET key.
Led 1 Alarm (Red)
= ON = Disablement led ON with delay (by default)
Led 2 Disablement (Yellow)
= ON = Disablement led OFF with delays

5.4.7 Cancel delays with 2 zones in alarm

In case of zones alarms with delays, the zones in alarm can be configured to cancel delays.
Configure: 2 Zones cancel delays
Select the configuration menu of delays cancellation with 2 zones in alarm by pressing at the
same time the following keys:
( KEYPAD ACCESS=ON + MUTE BUZZER=ON)
The cyclic change of the function is made by pressing the RESET key.
Led 1 Alarm (Red)
= ON = 2 Zones in alarm DO NOT cancel delays (by default)
Led 2 Disablement (Yellow)
= ON = 2 Zones in alarm cancel delays
HLS-MN-025 v.04
www.honeywelllifesafety.es
www.hoeywelllifesafety.es
EN54-2: Delay on/off and Disablement led
Change
option
Reset push-button: Change Option (Access level 3 - Configuration)
Change
option
Reset push-button: Change Option (Access level 3 - Configuration)
Configuración
Installation and Operating Manual
Page 42