Www.honeywelllifesafety.es - Honeywell NFS Supra Installation And Operating Manual

Conventional fire alarm control panel
Table of Contents

Advertisement

NFS Supra
Sounders delayed (yellow): This led indicates that the sounders are programmed with delays for detector alarms in a zone.
-Led On: There are delays configured for sounders.
-Led flashing: Delays operating. When delays are finished, sounders are activated. Press the Delay On/Off key to stop the
operating delays. Sounders are activated immediately when there is an alarm in the system.
Power Supply Fault (Yellow):
-Led On: Power supply fault. Check the 220 Vac power supply and batteries, the fuses of both and the Aux. 24V output. When the
fault cause has been cleared, press the Reset key (Access level
Auxiliary Power Supply Fault (Yellow):
-Led On: Auxiliary Power Supply Fault. Check the 24V AUX fuses.
(Access level 2) to make the system return to its normal state.
Note: This fault can cause, field device malfunction if they are powered by this output.
System Fault (yellow): A serious system fault has been detected.
-Led On: System fault. Switch off the 220V power supply and batteries until the Power led is off and connect the power supply
again. If the fault continues, contact your supplier.
Note: In case that the external relays or communication boards are installed but not communicating with the NFS supra control
panel, the system fault led will light.
HLS-MN-025 v.04

www.honeywelllifesafety.es

www.hoeywelllifesafety.es
This led indicates that there is a fault in the control panel power supply.
2) to make the system return to its normal state.
This led indicates that there is a fault in the Auxiliary 24V output.
When the fault cause has been cleared, press the Reset key
Installation and Operating Manual