5.5.1 Check/Change special functions configuration:
Switch off the control panel (Mains supply and battery disconnection), then connect the
(PROG) jumper and connect again the control panel as usual. Special functions leds will be lit,
according to the current configuration, as showed below:
Keypad Access led
Silence/Resound led =ON
Delay On/Off led
Mute Buzzer led
Zone 3 fault led
HLS-MN-025 v.04
www.honeywelllifesafety.es
www.hoeywelllifesafety.es
= ON
= Latched faults. Faults need to be RESET (by
default)
= OFF =
Resettable
faults.
automatically when fault has disappeared
= Power supply faults are indicated (by
default)
=OFF = Power supply faults are not indicated
=ON = Battery faults are indicated (by default)
=OFF= Battery faults are not indicated.
=OFF= Port RS-232 not monitored (by default). (only
from MK-VSN/TG)
=ON = Port RS-232 monitored (by default). (only from MK-VSN/TG)
=OFF= Fault relay activates only with General fault.
=ON = Fault relay activates with fault and digital input
activated
Faults
RESET
Configuration