5.4.3 Delay 2 (Secondary delay – Alarm inspection)
Delay 2: Period of time available to check the alarm cause after pressing MUTE BUZZER push-
button. After this time, sounders will activate. It is possible to configure a period of time from 0
sec. (only delay 1 is performed) to 10 minutes at 1 minute intervals.
Delay 2 configuration:
Select Delay 2 by pressing DELAY ON/OFF=ON
Then press RESET push-button to change cyclically the led that has to be on and, consequently
to change the period of time.
No leds on
Led 1 Alarm (Red)
Led 2 Disablement (Yellow)
Led 3 Test (Yellow)
Led 4 Power (Green)
Led 5 General Fault (Yellow)
Led 6 Earth fault (Yellow)
Led Sounders fault/Disabled (Yellow)
Led 8 Power Supply (Yellow)
Led 9 Auxiliary P.Supply F.(Yellow)
Led 10 System Fault (Yellow)
At level 1 or 2, DELAY ON/OFF push-button can be pressed in order to cancel
operating delays
Alarm inspection (delay 2) starts after pressing the mute key confirmation period (Delay 1).
The sounder and relay cards outputs operation depends on the control matrix.
HLS-MN-025 v.04
www.honeywelllifesafety.es
www.hoeywelllifesafety.es
= OFF= 0s only delay 1 (by default)
= ON = 1 min
= ON = 2 min
= ON = 3 min
= ON = 4 min
= ON = 5 min
= ON = 6 min
= ON = 7 min
= ON = 8 min
= ON = 9 min
= ON = 10 min
Configuración
increase
Reset push-button: Change Option
1 min
(Access level 3 - Configuration)
Maximum Delay, Delay 1 + Delay 2, is 10 minutes
(EN54-2).
If there is any delay configured, the disablement led will be
illuminated.
The delay can be cancelled or disabled the Delay ON/OFF Led
is iluminated