Conventional fire alarm control panel
Table of Contents

Advertisement

NFS Supra
ZONE INDICATORS
The system has a number of alarm detection zones which will correspond, in general, with
particular areas of the protected building.
In case of incidence in one of these zones, the zone led indicator, indicates their status. In case
of Fault, Disablement or Test in one zone, besides the yellow zone LED, the general state LED
of the specific event will light. If you enable access to Level 2 (Operator), LED zone will flash
latched (with the same frequency) as the general status LED of the relevant zone.
Zone Alarm (Red):
alarm condition in this
-Led flashing: There is a detector in alarm.
-Led On: There is a call point in alarm.
Check the alarm cause and press the Reset key (Access level 2) to make the system return to its normal status.
Zone Fault/Disabled/Test (Yellow):
-
Led flashing quickly (and Fault led also on): The zone is in fault condition. Check the zone wiring. Once the fault cause has been
cleared, press the Reset key (Access level 2) to make the system return to its normal status.
-Led On (and Disablement led on too). The zone is disabled. Enable the zone by pressing the Zone key (Access level 2) until the
zone yellow led is off.
-Led On (and Test led On too) / (flashing slowly with test led On in Access level 2): The relevant zone is being tested. Press the
Zone key (Access level 2) until the zone yellow led is off.
HLS-MN-025 v.04

www.honeywelllifesafety.es

www.hoeywelllifesafety.es
This led indicates that there is a device under
zone.
The relevant zone is in fault, test or disabled.
Operation
Indicadores
de Zonas
Installation and Operating Manual