1.4 FRONT PANEL LED INDICATIONS

ALARM (red):
It flashes if there is at least one device in alarm status and it has not been recognised yet.
It is permanently on if all alarm events have been recognised.
PREALARM (red):
It flashes if there is at least one device in pre-alarm status and it has not been recognised
yet. It is permanently on if all pre-alarm events have been recognised.
REMOTE ALARM ACTIVATED (red):
It is permanently on if the output to the fire alarm transmission devices (telephone dial)
has been activated.
SILENCE SOUNDER (yellow):
It is on after the sounder silencing command has been performed.
DELAY ACTIVATED (yellow):
It is on if the immediate output activation has been disabled; this applies to type C
(sounder output) and type E (alarm transmission via telephone dial) outputs. When this
delay is activated, in the event of an alarm the system delays the abovementioned outputs
for the programmed times. During the delay time the LED flashes and it is possible to
reset the current delay via the "reset delay" button with user level 1 authorisation.
EVACUATION (yellow):
It is on after the evacuation function has been activated.
TEST (yellow):
It is on during the zone walk test.
POWER (green):
It is permanently on if the control unit is powered (230 V AC or battery charger).
FAULTS (yellow):
It flashes if there is at least one fault of any type and it has not been recognised yet.
It is on if all faults have been recognised.
SYSTEM (yellow):
It is on if there is at least one system fault (watch dog, CRC memory error, etc.).
POWER SUPPLY (yellow):
It is on if there is a power supply fault.
EARTH FAULT (yellow):
It is permanently on if the loop/main positive or negative are earthed.
DISABLEMENTS (yellow):
It is on if there is at least one zone or point disabled in the system.
SOUNDER (yellow):
It is on if the siren output is disabled. It flashes if the siren output is in fault condition.
FAULT TRANSMISSION (yellow):
It is on if the fault transmission output is disabled (telephone dial). It flashes if the fault
transmission output is in fault condition.
ALARM TRANSMISSION (yellow):
It is on if the alarm transmission is disabled (telephone dial). It flashes if the alarm
transmission output is in fault condition.
EXTINGUISHING (yellow):
It is on if the output towards the automatic fire-fighting system (UDS) is disabled. It
flashes if the fire-fighting control output is in fault condition.