Control Panel Installation
5.
Connect a printer to the 5824 as shown below.
4.12.1 Selecting 5824 Options
Configuring the 5824 includes the following steps:
1.
Add the module to the system. JumpStart will add the module automatically (see Section 8.2). You can also add it manually (see
Section 8.2.2).
2.
Select a name, if desired.
3.
Select options for the printer and the output port. See below.
Printer and Output Port Options
The printer is for ancillary use only.
1.
From the Main Menu, select 7 for Program Menu.
2.
Select 1 for Module.
3.
Select 1 for Edit Module.
4.
From the list that displays, select the desired 5824 module.
5.
Press ENTER to bypass the next two screens. A screen similar to the one shown below will display.
Monitor Printer=Yes
Output Port=Parallel
Event Logging=NO
6.
Select options for the printer as needed for your installation. Most printers are parallel.
7.
If you are using a serial printer, use the next screen to select serial port options as required for your printer. Refer to your printer manual
if you need more information.

4.13 5880 LED I/O Module

The 5880 is an LED driver board that can be used in a wide variety of applications, including as an interface with most customized floor plan
annunciator boards. The 5880 can drive up to 40 LEDs and has one PZT controller. The 5880 also has eight inputs for dry contact monitor-
ing. The following sub-sections describe hardware installation. Refer to Section 8 for programming information.
48
FACP
supervised,
power-limited,
Class B
Figure 4.31 5824 Connection to the Panel
More
Figure 4.32 Selecting Printer and Output Port Options
Option
Baud Rate:
75 - 19200
Data Bits:
5 - 8
Stop Bits:
0.5, 1, 2
Parity:
None, Even, Odd
Table 4.7 Serial Printer Options
IFP-300 Series Manual — P/N LS10145-001SK-E:C 4/6/2022
DIP switches
5824
Select Yes if printer should be supervised for
Out-of-Paper and Offline conditions.
Select type of printer, Parallel or Serial.
Choices
5880 LED I/O Module
parallel
connectors for
connection to
printer
serial