Honeywell NFS Supra Installation And Operating Manual page 37

Conventional fire alarm control panel
Table of Contents

Advertisement

NFS Supra
Zone type configuration:
Select the desired zone by pressing the relevant push-button ZONE=ON (Red or Yellow). The
zone led will be lit in red or yellow, depending on the short also section fault/alarm by short
circuit.
Zone Short Circuit Configuration by pressing the zone key:
Zone = ON (Yellow) = Short circuit is fault
Zone = ON (Red) = Short circuit is alarm
Change zone type cyclically by pressing RESET.
Zone Configuration
Led 1 Alarm Red
= ON = Normal (By default)
Led 2 Disablement Yellow
=ON= Delay contact 30s. (470). Zener immediate activation
Led 3 Test yellow
=ON= Verification. 10 minutes.
Led 4 Power green
=ON= Delay contact 30 sec. (470
The sounder and relay cards outputs operation depends on the zone configuration
associated with these outputs.
HLS-MN-025 v.04
www.honeywelllifesafety.es
www.hoeywelllifesafety.es
and Zener)
Configuration
Reset
push-button:
(Access Level 3 configuration)
Note: The zone led will be lit in red or yellow,
depending on the short circuit option configuration
for zones alarm or fault
Installation and Operating Manual
Change
Option
Page 37