VENTING ARRANGEMENT FOR VERTICAL TERMINATIONS
The shaded area in the diagram shows all allowable combinations
of straight vertical and offset to vertical terminations, using one
90
o
elbow, with Rigid Pipe Venting Systems.
o
Two 45
elbows equal to one 90
o
starting 45
elbow at the fl ue collar.
•
Vent must be supported at offsets.
•
Minimum distance between elbows is 1 ft. (305mm).
•
Maintain clearances to combustibles as listed in the
"Clearances" section.
•
Horizontal vent must be supported every 3 feet.
•
Firestops are required at each fl oor level and whenever
passing through a wall.
•
Must use optional rigid pipe adaptor (Part# 510-994)
when using rigid pipe vent systems.
•
Refer to the "Vent Restrictor Position" section for
details on how to change the vent restrictor from the
factory setting of Set 0 to Set 1 or Set 2 if required.