Venting Arrangement For Vertical Terminations-Inline Power Vent - Regency Fireplace Products City Series Owners & Installation Manual

Direct vent gas power vent fireplace, single sided
Hide thumbs Also See for City Series:
Table of Contents

Advertisement

CV72EPV/CB72EPV/CB40EPV/CC40EPV/CV40EPV/CB60EPV/CV60EPV
Inline Power Vent Vertical or Hortizontal Installation Instructions
Venting Arrangement for Vertical Terminations - Inline Power Vent

Venting Arrangement for Vertical Terminations-Inline Power Vent

Vertical venting with straight vertical venting and or with a max. of six (6) 90
Vertical venting with straight vertical venting and/or with a max. of six (6) 90
RIGID PIPE: MUST USE RIGID PIPE ADAPTOR 510-994.
Note: Rigid pipe is approved for up to 72 feet (21.95 m).
Note: Flex pipe is approved for up to 40 feet (12.19 m) using 2 X 946-756--20 foot flex kits.
Two 45
o
elbows equal to one 90
Vent must be supported at offsets.
Minimum distance between elbows is 1 ft. (0.3 m).
Maintain clearances to combustibles as listed in the
"Clearances" section.
Horizontal vent must be supported every 3 feet (0.91 m).
Firestops are required at each floor level and whenever
passing through a wall.
Restrictor set on 0 (fully open) regardless of vent run.
Inline power vent location restrictions:
Minimum 4 ft (1.22 m) from the unit.
Minimum 1 ft (0.3 m) prior to an elbow.
Minimum 1 ft (0.3 m) following an elbow.
Minimum 2 ft (0.61 m) prior to a termination cap.
Minimum 2 ft. from inline PV to termination cap.
Minimum 4' from top of unit to inline PV.
Max. of 72' (21.95 m), using up to six 90
(Note: example shows two 90
No negative runs.
Note: The inline power vent must be installed within the confines
of the home/structure.
920-210c
o
elbow.
0
elbows
elbows).
0
Min. 4' (1.22 m) from top of unit
Elbows (1 - 90
o
o
Elbows (1 - 90
Max. of 72' (21.95 m), using up
(Note: two 90 elbows shown.)
to inline PV
2
installation
2 - 45
)
o =
o
o =
2 - 45
o
)
Min. 2' (0.61 m) from inline
PV to termination cap
Min. 4' (1.22 m) from
top of unit to inline PV
to six 90 elbows
0
0
Min. 2' (0,61 m) from inline PV
to termination cap
CV40EPV City Series |
10.04.21
41