10.5 LOCATION

Avoid locating the terminals where the fl ue gas could become stagnant and allow recirculation into the
combustion air intake.
Avoid locating the terminal in locations where dripping condensate may cause problems such as sidewalks,
patios, above planters, near windows where exhaust gases may cause fogging, etc.
Avoid locating the termination too close to shrubs and other vegetation. The condensate may stunt or kill them.
Caulk all cracks, seams or joints within a 6 foot radius of the termination.
Do not terminate under a deck unless there is adequate clearance to prevent damage from the fl ue gases.
A termination may be located at the end of a patio deck. Piping running beneath the deck must be suitably
insulated and suspended in a manner to prevent condensate from collecting and freezing.
Do not locate the terminal on the side of the building facing the prevailing winter winds.
IMPROPER LOCATION OR INSTALLATION CAN RESULT IN STRUCTURAL DAMAGE TO
THE BUILDING, DAMAGE TO THE EXTERIOR FINISH OF THE BUILDING, OR MAY ALLOW
RECIRCULATION OR FREEZING OF THE FLUE GASES ONTO OR INTO THE COMBUSTION
MOISTURE IN THE FLUE GASES CONDENSES AS IT LEAVES THE TERMINALS. THIS
MOISTURE CAN FREEZE ON EXTERIOR WALLS, SOFFITS, AND OTHER NEARBY
The vent terminal should be located no fewer than 6 feet from an inside corner formed by two exterior walls. A
10 foot distance is recommended.
Recommended clearance for overhangs is a minimum of 1 foot vertically for each foot horizontally up to 6 feet.
Any adjacent painted surfaces should be in good condition; no cracks, peeling paint, etc. If wooden surfaces that
may be periodically exposed to fl ue gases are present, consider treating with a sealer.

10.6 MULTIPLE VENTING

IMPORTANT
WHEN INSTALLING MULTIPLE FURNACES IN CLOSE PROXIMITY, EACH REQUIRES
DEDICATED COMBUSTION AIR AND EXHAUST VENTING.
COMMON VENTING IS PROHIBITED!!
If two of these furnaces are to be installed in close proximity, the combustion air intake and exhaust
terminations may be installed as shown in Figures 12 and 13.
FIGURE 12 - MULTIPLE VENTING (STANDARD
W415-1064 / 11.11.11
OBJECTS. SOME DISCOLORATION IS TO BE EXPECTED.
:
HORIZONTAL)
!
CAUTION
AIR INTAKE.
FIGURE 13 - MULTIPLE VENTING (STANDARD
!
VERTICAL)