Installation In Upflow Position; Air Conditioning - Napoleon 9700 SERIES Installation And Operating Instructions Manual

Two stage high efficiency (condensing) forced air gas furnace
Table of Contents

Advertisement

12
4.3

INSTALLATION IN UPFLOW POSITION

UPFLOW INSTALLATION: Vent positioning, pressure switch location and drain locations shall be performed in
accordance with instructions in the appropriate sections of this manual.
NON-SUSPENDED INSTALLATION: Maintain clearances to combustibles as outlined in Figure 1, Table B. The
furnace must be supported in such a way as to not allow twisting or sagging of the cabinet.
IMPORTANT
THE FURNACE MUST BE INSTALLED ON A LEVEL SURFACE. IT IS RECOMMENDED
THAT THE REAR OF THE FURNACE BE ELEVATED 1/4" HIGHER THAN THE FRONT
TO FACILITATE PROPER CONDENSATE DRAINAGE.
IF THE FURNACE AND AIR CONDITIONER IS LOCATED ABOVE A FINISHED SPACE,
INSTALL A DRAIN PAN UNDERNEATH THE UNIT.
NOTE
THIS FURNACE IS CERTIFIED FOR UPFLOW INSTALLATION ONLY.
This furnace is approved for installation in attics, alcoves, utility rooms, closets and crawl spaces. If this
furnace is to be installed in a utility room, be sure that it is located in such a way as to allow access for
servicing or the removal of other appliances installed in the room (hot water heater, for example). It is not
permissible to use a rear return on this appliance. Use only side and bottom returns.
4.4

AIR CONDITIONING

This furnace may be used as part of an air conditioning system. The furnace wiring and control system is "air
conditioning ready." There are the following factors to consider:
The air conditioning evaporator coil must be downstream of the heat exchanger. The cooled air passing
over the warmer heat exchanger tubes can cause condensation inside the tubes, resulting in corrosion and
premature failure.
A parallel duct system can be installed to direct the air from the furnace through the evaporator coil only. Use
dampers or other means to bypass the heat exchanger. If (summer/winter) dampers are used, they should be
interlocked to prevent system operation unless the dampers are in the full open or full closed position.
NOTE
If installing a two stage air conditioning system, clip the JW38 jumper wire between Y and Y2 on the furnace
control board.
W415-1064 / 11.11.11
: