Vent Termination - Napoleon 9700 SERIES Installation And Operating Instructions Manual

Two stage high efficiency (condensing) forced air gas furnace
Table of Contents

Advertisement

22
DO NOT CONNECT FURNACE TO A CHIMNEY OR FLUE SERVING OTHER APPLIANCES OR A
9.1

VENT TERMINATION

Horizontal vents should pass through
the exterior wall. Figure 8 shows
a standard horizontal vent detail.
Terminate the vent approximately 8" or
more from the wall.
Exterior vent pipe greater than 24"
should be insulated with ½" insulation
to prevent moisture from freezing within
the pipe and accumulating.
Size the exhaust pipe as specifi ed in
Table 4 - Direct and Non-Direct Vent
Lengths. This table lists the maximum
allowable length of pipe with respect to
the number of 90° elbows used. For the
purposes of this calculation, one 90°
elbow is equivalent to two 45° elbows.
Avoid locating the terminal in locations
where dripping condensate may cause
problems such as sidewalks, patios,
above planters, near windows where
exhaust gases may cause fogging, etc.
Avoid locating the termination too close
to shrubs and other vegetation. The
condensate may stunt or kill them.
W415-1064 / 11.11.11
FIGURE 8 - STANDARD (STRAIGHT) HORIZONTAL
VENT DETAIL
*18" MIN. FOR COLD CLIMATES (SUSTAINED 0°F (-17°C) FOR 24 OR MORE
CONSECUTIVE HOURS
WARNING
!
SOLID FUEL BURNING APPLIANCE.
TABLE 4 - DIRECT AND NON-DIRECT VENT LENGTHS
Maximum Allowable Length Of Exhaust Or Intake. Minimum Vent Length 15 ft.
or equivalent.
INPUT
PIPE
K/Btu/hr
SIZE
60
2
3
2
80
3
2
100
3
120
3
NOTE
When 1½" or 3" pipe is used, exit the cabinet with 2" pipe. Reduce or
increase immediately after exiting the cabinet on both intake and exhaust.
RECOMMENDED
*
!
NUMBER OF 90° ELBOWS
0
1
2
3
4
5
60
55
50
45
40
35
75
70
65
60
55
50
100
95
90
85
80
75
50
45
40
35
30
25
100
95
90
85
80
75
50
45
40
35
30
25
100
95
90
85
80
75
100
95
90
85
80
75
NOTES
6
1. Count concentric vent
30
fi tting as straight pipe.
2. Use medium or long
45
sweep elbows where
possible.
70
3. One 90° elbow is
equivalent to two 45°
20
elbows.
70
4. For direct vent, the
listed lengths are
allowed for each vent
20
(intake and exhaust).
70
5. For non-direct vent,
the listed lengths are al-
lowed for exhaust. The
intake should have a
70
1½" or 2" snorkel intake
fi tting. (Figure 7)