Honeywell SDC Service Manual page 94

Smile sdc heating and district heating controller
Table of Contents

Advertisement

Operation
Para-
Designation
meter
12
Minimum
temperature limit
13
Maximum
temperature limit
14
Temperature
increase of heating
circuit
15
Extended pump
over-run
16
Screed function
23
Room control
C-factor (SDW 30
only)
24
Room control T
(SDW 30 only)
25
Holiday operating
mode
26
Room setpoint
ramp
41
Switch-on
optimisation
42
Min. pre-heat time
43
Max. pre-heat time Setting value of parameter 42 to
44
Min. jump back
temperature
45
Without room
sensor
94
Setting range / Setting values
10°C to setting value of
parameter 13
Setting value of parameter 12 to
Setting value of parameter 30 in
"Heat generator" menu (OEM
maximum limit)
–5 ... 20 K
0 ... 60 min
OFF
1
Functional heating
2
Screed-drying heating
1 ... 100
5 ... 240 min
n
STBY
Standby
RED
Lowering operation
OFF, 0.5 to 60 K/h
OFF
1
Adaption off
2
Adaption on
3
Adaption restart
0 ... setting value of parameter 43 0,5
30 h
0 ... 30°C
0 ... 10°C
SDC / DHC
Factory
Setting
setting
20
75
Direct
heating
circuit = 0
5
OFF
8
35
STBY
OFF
OFF
5
5
1
EN2H-0221GE51 R0812