NOTE
Function
Economy interval
(pulse)
Economy interval
(period duration)
EN2H-0221GE51 R0812
Tank priority (no heating demand):
Connection immediately with minimum delay
Reversion with configured delay P3
Tank parallel operation (combined operation: hot-water
loading/heating)
Connection up to the stage of parameter 09 with minimum
delay for hot-water loading
In case of further need via heating, further connection with
configured delay of parameter 02
Reversion with configured delay parameter 03

Circulation pump (CIR.)

This function is only available, if a variable output is assigned to a
circulation pump
The output controls a hot-water circulation pump.
The use of the economy interval minimises the usual circulation
losses owing to adjustable switch-on intervals during operation
and determines the standstill time of the hot-water circulation
pump within an adjustable period (economy interval).
This parameter determines the length of the period and hence the
duration of the pause in a circulation pump pulse operating mode.
Economy interval
Pause
interval
Pulse
The switching-on degree is calculated from the ratio:
n = Pulse time/Period duration x 100 (%)
Example:
= Economy interval
Hydraulic Components
- Economy
Period duration
195