Cascading" Menu (Cascade) - Honeywell SDC Service Manual

Smile sdc heating and district heating controller
Table of Contents

Advertisement

Operation
5.4.13
Para-
Designation
meter
01
Switching
differential
02
Connection delay
03
Switch-off delay
04
Switchover power
of stage sequence
05
Stage reversal
06
Guidance stage
07
Peak-load stage
08
Switchover of base
load with grouping
09*
Quick hot-water
connection
110

"Cascading" menu (CASCADE)

The parameters in this menu refer solely to the parameters that
are associated with the cascading of multiple heat generators.
This selection is only available if multiple heat generators exist in
the control system.
Setting range / Setting values
0.5... 30 K
0 ... 200 min
0 ... 60 min
10 ... 100 %
OFF, 1 to 250 h
1 ... maximum number of stages
OFF, 2 ... maximum number of
stages
All heat generators are numbered
consecutively within the cascade.
The total quantity determines the
maximum number of stages.
OFF, ON
OFF, 1 ... maximum number of
stages
* OEM
SDC / DHC
Factory
Setting
setting
4
0
0
65
OFF
1
OFF
OFF
OFF
EN2H-0221GE51 R0812