Honeywell SDC Service Manual page 177

Smile sdc heating and district heating controller
Table of Contents

Advertisement

SDC / DHC
Hydraulic Components
Switch-on: Flow setpoint < (current room setpoint + heating limit
setting + 2 K)
Example:
Room setpoint = 22°C, heating limit setting = 2 K
Switch-off at flow setpoint 24°C (22°C + 2 K)
Switch-on at flow setpoint 26°C (22°C + 2 K + 2 K)
Boundary conditions
The SUMMER SWITCH-OFF function ("System Parameters"
menu, parameter 04) has priority over the HEATING LIMIT
function.
The FROST PROTECTION function ("System Parameters" menu,
parameter 05) has priority over the HEATING LIMIT function.
EN2H-0221GE51 R0812
177