Heat Generator" Menu - Honeywell SDC Service Manual

Smile sdc heating and district heating controller
Table of Contents

Advertisement

SDC / DHC
Para-
Designation
meter
Heat-
Heating circuit
ing
name
circuit
name
5.4.6
Para-
Designation
meter
01
Design
02
Start-up protection
(not if parameter
01 = OFF)
03
Minimum tem-
perature limit (not
if parameter 01 =
OFF)
04
Maximal
temperature limit
(not if parameter
01 = OFF)
EN2H-0221GE51 R0812
Setting range / Setting values
00000 ... ZZZZZ
* OEM
"Heat generator" menu (HEAT GENER.
The parameters in this menu refer to the type of the respective
heat generator and the associated specific control functions.
Setting range / Setting values
OFF
Without heat generator
1
Oil/gas - one stage
2
Oil/gas - two stages
3
Oil/gas - 2 x one stage
4
Modulating burner
5
Open Therm
OFF
No start-up protection
1
Unlimited start-up
protection
2
Start-up protection
controlled by weather
conditions
3
Start-up protection
disconnected
5°C to setting value of parameter
04
Setting value of parameter 03 to
setting value of parameter 30
(OEM maximum limit)
Operation
Factory
Setting
setting
Factory
Setting
setting
1
1
38 (5 with
automatic
operation)
80
99