Honeywell SDC Service Manual page 108

Smile sdc heating and district heating controller
Table of Contents

Advertisement

Operation
Para-
Designation
meter
01
Minimum
temperature
02
Maximum
temperature
03
Boiler temperature
increase
04
Buffer switching
differential
05
Forced discharge
06
Follow-up switch-
on differential
07
Follow-up switch-
off differential
08
Buffer start-up
protection
09
Buffer discharge
protection
108
Setting range / Setting values
5 °C to setting value of parameter
02
Setting value of parameter
01 to 95 °C
–10 to 80 K
1 to 70 K
OFF
1
In process water tank
2
In heating circuits
OFF, (setting value of parameter
07 + 2 K) to 50 K
1 K to (setting value of parameter
06 – 2 K)
OFF
No start-up
protection
Switching
5 ... 20 K
differential
OFF
No discharge
protection
ON
Discharge protection
active
SDC / DHC
Factory
Setting
setting
20
80
0
2
OFF
10
5
ON
5 K
ON
EN2H-0221GE51 R0812