Hot-Water Circuit" Menu (Dhw) - Honeywell SDC Service Manual

Smile sdc heating and district heating controller
Table of Contents

Advertisement

SDC / DHC
5.4.3
Para-
Designation
meter
Hot
Hot water at night
water
Legio
Legionella
protect
protection day
ion day
03
Legionella
protection time
04
Legionella
protection
temperature
05
Transducer for hot-
water circuit
06
Maximum
temperature limit
for hot water circuit
EN2H-0221GE51 R0812

"Hot-water circuit" menu (DHW)

This menu contains all parameters required to program the
hot-water circuit, except the switch time programs.
Setting range / Setting values
10°C to normal hot-water
temperature
OFF
No legionella protection
Mon to
Legionella protection on
Sun
specified day of week
ALL
Legionella protection
every day
00:00 ... 23:00 hours
10 °C to setting value of
parameter 06
1
Hot-water circuit
temperature sensor
2
Hot-water circuit
temperature controller
(thermostat)
20°C to heat generator maximum
temperature
If parameter 07 = 7:
20 to 90°C.
In automatic mode, from hot-
water circuit minimum
temperature.
Operation
Factory
Setting
setting
40
OFF
02:00
65
1
65
89