Honeywell SDC Service Manual page 101

Smile sdc heating and district heating controller
Table of Contents

Advertisement

SDC / DHC
Para-
Designation
meter
13
Lead time of boiler
circuit pump or
parallel heat
generator enable
(only with
appropriate
configuration in the
"Hydraulics"
menu)
14
Follow-up time of
boiler circuit pump
(only with
appropriate
configuration in the
"Hydraulics"
menu)
15
Follow-up time of
feeder pump (only
with appropriate
configuration in the
"Hydraulics"
menu)
16
Exhaust gas
temperature
monitoring (only
with appropriate
configuration in the
"Hydraulics"
menu)
17
Exhaust gas limit
value (only with
appropriate
configuration in the
"Hydraulics"
menu)
EN2H-0221GE51 R0812
Setting range / Setting values
0 ... 10 min
0 ... 60 min
0 ... 60 min
OFF
Display of exhaust gas
temperature only
0 ... 60
Heat generator lock if
min
limit value is exceeded
for set time
SLT
Heat generator lock if
limit value is exceeded
50 ... 500°C
Operation
Factory
Setting
setting
0
2
2
OFF
200
101