Control Functions
6.8.1
6.8.1.1
Function
Light construction
Medium construction
Heavy construction
See also
120
6.8
General functions and their operation
Outside temperature sensing
Building type
This parameter takes into account the relevant building type by
means of various calculation methods for the determination of the
outside temperature mean value according to the setting.
The mean value is obtained over a period of 2 hours.
Application:
Wooden houses, lightweight brick buildings
The mean value is obtained over a period of 8 hours.
Application:
Medium-weight masonry in hollow blocks or bricks
The mean value is obtained over a period of 24 hours.
Application:
Heavy masonry in tuff or natural stone
5.4.4 "Direct heating circuit" menu (UNMIXED CIRC), Pg. 92 and
5.2.5 "Direct Heating Circuit" / "Mixed Heating Circuit 1" / "Mixed
Heating Circuit 2" menu, Pg. 78
SDC / DHC