85 FLOW ThERMIsTOR FAULT - CONTACT INsTALLER
Remove the Flow Thermistor from the CH Flow Pipe
and disconnect the wires.
Check the resistance using a suitable multimeter
connected across the thermistor's terminal pins.
At 25
C
expect
o
At 60
C
expect
o
At 85
C
expect
o
Is the Thermistor value correct?
Is there continuity between the PCB and the Thermistor?
Replace PCB
86 RETURN ThERMIsTOR FAULT - CONTACT INsTALLER
Remove the Return Thermistor from the CH Return
Pipe and disconnect the wires.
Check the resistance using a suitable multimeter
connected across the thermistor's terminal pins.
At 25
C
expect
o
At 60
C
expect
o
At 85
C
expect
o
Is the Thermistor value correct?
Is there continuity between the PCB and the Thermistor?
Replace PCB
60
FAULT FINDINg
9,700 - 10,300
Ohms
2,400 - 2,600
Ohms
1,000 - 1,100
Ohms
YES
YES
9,700 - 10,300
Ohms
2,400 - 2,600
Ohms
1,000 - 1,100
Ohms
YES
YES
NO
Fit a new Thermistor
NO
Check and replace wiring as necessary
NO
Fit a new Thermistor
NO
Check and replace wiring as necessary
+
Ideal Logic
Combi -
Installation and Servicing