Connect Input/Output Power; Replacing A Power Distribution Box; Distribution Box Electrical Connections; Figure 3 30A Branch Circuit Breaker Connection Diagram - Liebert GXT2-6000 RT208 User Manual

120/208v; 120/240v
Table of Contents

Advertisement

6.3

Connect Input/Output Power

The UPS ships with the basic hardwire box attached. If an
optional model is to be used, remove the standard box and
install the optional box using the three captive mounting
screws marked in the illustration, below, right.
6.3.1

Replacing a power distribution box

Whenever a power distribution box is not attached to a UPS,
the cover must be slid over the electrical connectors to prevent
damage or injury.
1. On the power distribution box attached to the UPS,
locate the three captive mounting screws holding the box
to the UPS (see illustration above, right).
2. Turn the screws until the box can be pulled away from the
UPS. Exercise care to avoid removing screws from the
hardwire box.
3. On the replacement power distribution box to be
attached to the UPS, loosen the cover over the electrical
connectors by backing out the three screws one turn each.
4. Slide the cover open to expose the electrical connectors.
5. Gently retighten the three screws loosened in Step 3.
6. Align the connectors on the box and UPS.
7. Push the box into place.
8. Holding the box firmly against the UPS, tighten the three
captive mounting screws until the box is secure. Do not
overtighten.
6.3.2

Distribution Box Electrical Connections

Electrical connections are made through a removable power distribution box that attaches to the rear
of the UPS.
The installer must provide a 30A branch circuit breaker. The input circuit breaker on the distribution
box and the output circuit breaker on the rear fixed-panel of the UPS disconnect all power between
the main cabinet and the distribution box.
Models equipped with a manual bypass switch pass utility power directly to the bypass switch from
the input terminal block. The input circuit breaker on the distribution box does not disconnect power
from the manual bypass switch.
Figure 3
30A branch circuit breaker connection diagram
PD-HDWR Distribution Box
Input
Utility
30A External
Branch Circuit
Breaker
30A UPS Output
Circuit Breaker
UPS - PFC, Battery, Inverter
Output
30A Input
Circuit
Breaker
Slide
cover
over
connec-
tors
Loosen screws
to move cover
PD-HDWR-MBS Distribution Box
Input
Utility
30A External
Branch Circuit
Breaker
UPS - PFC, Battery, Inverter
14
Installation and Configuration
Mounting screws
for removable box
Byp
Output
30A Input
Inv
Circuit
Breaker
30A UPS Output
Circuit Breaker