External Battery Cabinet Installation - Liebert GXT2-6000 RT208 User Manual

120/208v; 120/240v
Table of Contents

Advertisement

6.2

External Battery Cabinet Installation

Optional Liebert external battery cabinets may be connected to the UPS to provide additional battery
run time. External battery cabinets are designed to be placed on one side of the UPS or stacked
beneath the UPS.
CAUTION
!
The external battery cabinet(s) are heavy (see 14.0 - Specifications). External battery
cabinets can be used in rack-mount or tower configuration. Take proper precautions when
lifting them.
CAUTION
!
Verify that the battery cabinet circuit breaker is in the OFF position. Do no energize the
battery cabinet at this time. When installation is complete, you will be instructed to turn on
the circuit breaker.
When the external battery cabinet is received, it should be inspected for freight damage. Report dam-
age to the carrier and your local dealer or Liebert representative.
To install an external battery cabinet:
1. For slide rail installations, first remove the top/side fin by sliding it forward and lifting it up.
Optional rack-mount handles are shipped with the external battery cabinet and may be installed
now. (Securing hardware and slide rails are sold separately. Please contact your local dealer or
Liebert representative for these additional options and any assistance needed.)
2. Fasten the slides into position with the screws according to the instructions included with the
slide rails.
3. Use the enclosed support bases for the tower option to
prevent the assembly from tipping over. One additional set
of support base extensions ships with each external battery
cabinet.
4. Connect the supplied external battery cabinet cable to either
of the connectors on the rear of the external battery cabinet,
then to the rear of the UPS.
5. The UPS is now equipped with additional backup battery
run time. For approximate battery run times, refer to Table
7 - Battery run times in this manual.
6. Do NOT turn on the battery cabinet circuit breaker at this
time. Please complete the remainder of the installation first.
NOTE
After installation is complete, you must use the included
configuration program to program the UPS for the
number of external battery cabinets connected.
Instructions for using the configuration program follow
in 8.0 - Configuration Program.
Support Base With
Spacers for External
Battery Cabinets
13
Installation and Configuration
UPS and Four External Battery
Cabinets With Support Base
+
+

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents