Product Warranty Registration; Table 11 External Battery Cabinet Specifications - Liebert GXT2-6000 RT208 User Manual

120/208v; 120/240v
Table of Contents

Advertisement

Table 11
External battery cabinet specifications
Model Number
Used w/ UPS Model
DIMENSIONS in (mm)
Unit (with bezel) W x D x H
Shipping W x D x H
WEIGHT lbs (kg)
Unit
Shipping
BATTERY PARAMETERS
Type
Qty x V x Rating
Battery Mfg / Part #
Back-Up Time
ENVIRONMENTAL
Operating Temp
Storage Temp
Relative Humidity
Operating Elevation
Storage Elevation
AGENCY
Safety
RFI/EMI
Transportation
14.1

Product Warranty Registration

To register for warranty protection:
• Visit the Quick Links section of our Web site at:
http://www.liebert.com
• Click on Product Warranty Registration and fill in the form.
If you have any questions, please contact us at:
US: 800-222-5877
Outside the US: 614-841-6755
upstech@liebert.com
GXT2-144VBATT
GXT2-6000RT208
3.5 x 24.2 x 17 (87 x 618 x 430)
10.5 x 27.2 x 23 (268 x 692 x 585)
93.6 (42.5)
105 (47.6)
Valve-regulated, non-spillable, flame retardant, lead acid
12 x 12V x 9.0 AH
Yuasa / REW 45-12 FR
See Table 7 - Battery run times
+32°F to +104°F (0°C to +40°C)
+5°F to +122°F (-15°C to +50°C)
0% to 95%, non-condensing
Up to 10,000 ft. (3000m) at 104°F (40°C) without derating
50,000 ft. (15,000m) maximum
UL 1778, c-UL Listed (Suitable for computer room applications)
FCC Part 15, Subpart B, Class A
ISTA Procedure 1A