Table 8
UPS specifications (continued)
Model Number
ENVIRONMENTAL
Operating Temp
Storage Temp
Relative Humidity
Operating Elevation
Storage Elevation
Audible Noise
AGENCY
Surge Immunity
Transportation
Table 9
Battery specifications
Model Number
DIMENSIONS in (mm)
Shipping W x D x H in. (mm)
WEIGHT lbs (kg)
Quantity x V x Rating
Battery Mfg / Part #
Back-Up Time
Recharge Time
Table 10
Power distribution box specifications
Model Number
Amp Rating
Input Power Connection
Output Power Connection
Input Branch Circuit Breaker
Model Number
Amp Rating
Input Power Connection
Output Power Connection
Includes:
Input Branch Circuit Breaker
Model Number
Amp Rating
Input Power Connections
Output Power Connection
Includes:
Input Branch Circuit Breaker
Up to 10,000 ft. (3000m) at 104°F (40°C) without derating
Safety
UL 1778, c-UL Listed (Suitable for computer room applications)
RFI/EMI
Unit
Shipping
Type
6 Hours to 90% capacity after full discharge into 100% load
Manual Bypass Switch with Indicator Lamps
L1-L2-G
L1-L2-N-G
L1-N-G
(2) 5-15/20R, T-type, receptacles with (2) 20A circuit breakers
L2-N-G
(2) 5-15/20R, T-type, receptacles with (2) 20A circuit breakers
Manual Bypass Switch with Indicator Lamps
GXT2-6000RT208
+32°F to +104°F (0°C to +40°C)
+5°F to +122°F (-15°C to +50°C)
0% to 95%, non-condensing
50,000 ft. (15,000 m) maximum
<55 dBA, at 1 meter from the rear
<50 dBA, at 1 meter from the front or sides
FCC Part 15, Subpart B, Class A
IEEE/ANSI C62.41 Category A & B
ISTA Procedure 1A
GXT2-144BATKIT
13.4 x 27.2 x 13.4 (340 x 690 x 340)
79 (35.8)
84 (38.1)
Valve-regulated, non-spillable, flame retardant, lead acid
12 x 12V x 9.0 AH
Yuasa / REW 45-12 FR
See Table 7 - Battery run times
PD-HDWR
24 Amps
4-Wire Hardwired, 8-10AWG
4-Wire Hardwired, 8-10AWG
30 Amp, Supplied by User
PD-HDWR-MBS
24 Amps
4-Wire Hardwired, 8-10AWG
4-Wire Hardwired, 8-10AWG
30 Amp, Supplied by User
PD-001
24 Amps
L14-30P on 10 foot cord
(1) L6-30R on a 300mm cord
(1) L14-30R on a 300mm cord
30 Amp, Supplied by User