Table 13
Battery retorque values
Battery
Battery
Manufacturer
Model No.
UPS12
UPS12
Dynasty
UPS12
UPS12
LS12
C&D Batteries
-
12G
HX205
HX300
Enersys
HX370
HX400
HX500
If you have a different model battery, contact Liebert Global Services for the required torque value.
To access battery cell terminals, disconnect the inter-tier cable and two shelf retaining screws. Once
disconnected, insulate (with protective boot or electrical tape) the cables to prevent accidental shorts.
The battery shelf can now be pulled out. Tighten each terminal connection to the retorque value.
When replacing a battery, the terminal connections must be cleaned and tightened. Disconnect and
insulate the cables connected to the battery. Secure each battery shelf with retaining screws when
maintenance is complete.
Rack-Mounted Batteries
If the UPS system uses a battery other than a factory-supplied Matching Battery Cabinet, perform
maintenance on the battery as recommended in the battery manufacturer's maintenance manual,
available on the manufacturer's Web site.
Table 14
Battery voltage record
Date
Float Voltage (Volts DC)
(To be completed by Liebert Global Services customer engineer at time of start-up)
Retorque
Value
-
-
270(FR)
32 lb
in.
-
-
310(FR)
52 lb
in.
-
-
370(FR)
52 lb
in.
-
-
475(FR)
100 lb
in.
-
-
100
100 lb
in.
-
17
100 lb
in.
-
60 lb
in.
-
60 lb
in.
-
60 lb
in.
-
60 lb
in.
-
60 lb
in.
Nominal Voltage (Volts DC)
105
Maintenance