Environmental Conditions; Table 17 Specifications Applicable To Environment - Liebert 1000kVA Operation & Maintenance Manual

100-1000kva, 60hz three phase multi-module
Table of Contents

Advertisement

5.2

Environmental Conditions

Table 17
Specifications applicable to environment
Enclosure
Recommended Operating
Temperature
Maximum Operating
Temperature
Minimum Operating
Temperature
Storage Temperature
Typical Battery
Temperature Requirements
Relative Humidity
Operating Elevation
Storage Elevation
Audible Noise, measured
5 feet from unit
Derating for Higher
Ambient Temperatures
(see Note 3)
Derating for Higher
Elevations
(see Note 4)
NOTES
1. This category of electronic equipment is agency rated for use in an atmosphere free of conductive particles. Some industrial facilities
may require a room air filtration system to keep the UPS free of excess moisture and contaminants.
2. The UPS system is designed to operate continuously at 40°C. However, design equipment life expectancy will be extended with lower
temperatures (25°C is recommended).
3. Ambient temperature is the maximum ambient temperature during any 24-hour period. For operation at higher ambient temperatures,
consult your Liebert sales representative or call Liebert Global Services at 1-800-LIEBERT.
4. Exercise care during installation to ensure unimpeded airflow through the UPS system. For operation at higher elevations, consult your
Liebert sales representative or call Liebert Global Services at 1-800-LIEBERT.
The UPS is housed in a NEMA-1 enclosure. The enclosure is designed for indoor use only
and is not to be subjected to falling objects or precipitation.
25°C ambient
40°C ambient (design temperature) without derating (see Notes 1- 3).
0°C
-
20°C to 70°C
Average annual temperature shall not exceed 27°C. Peak temperature shall not exceed
-
43°C during any 24
hour period. See battery manufacturer's recommendations.
0 to 95% without condensation
Sea level to 1219 meters (4000 ft.) without derating
Sea level to 15,000 meters (50,000 ft.)
62-69 dBA typical for 100-450kVA units
72 dBA typical for 500-750kVA units
75 dBA typical for 1000kVA units
98% at 45°C
96% at 50°C
93% at 55°C
Consult your Liebert sales representative regarding applications in high ambient
temperatures or call 1-800-LIEBERT. Special temperature sensors must be installed at the
factory.
Elevation-ft. (m)
5000 (1524)
5249 (1600)
5906 (1800)
6562 (2000)
7218 (2200)
7874 (2400)
8530 (2600)
9186 (2800)
9843 (3000)
109
% Derating @ 104°F (40°C)
Ambient (see Note 3)
98%
98%
97%
96%
95%
94%
93%
92%
90%
Specifications
% Derating @ 95°F (35°C)
Ambient (see Note 3)
100%
100%
99%
98%
97%
96%
95%
94%
92%