2.6
Environmental Conditions
The Liebert GXT3-10000T230 must be installed vertically, on a level and even surface and in an area
protected from extreme temperatures, water, humidity and the presence of conductive powder or dust
(see Table 11). Do not stack units; do not place any objects on top of a unit.
2.7
Access required
The area must have sufficient space for installation procedures and for routine maintenance. Access
doors must be sufficiently large to permit passage of the UPS.
2.8
Floor/Rack Loading
Ensure that the floor where the UPS/batteries will be installed will support the unit's weight (see
Table 10 for the unit's weight).
2.9
Inventory List
The Liebert GXT3-10000T230 comes with:
• CD containing:
• Liebert MultiLink
• Configuration Software
• User Manual
• USB cable
• Terminal block communication terminals
• Floor mount brackets
• Input power configuration jumpers
• Paralleling cable
2.10
Clearance
The UPS is fitted with wheels for ease of movement over short distances. Leave 300mm (12in.)
around the sides and rear of the unit to allow a flow of air and to provide access for any routine main-
tenance that may involve removal of the panels.
2.11
Repacking the UPS
To repack the UPS, proceed as follows:
1. Do not pack the equipment until at least six hours have elapsed since the last recharge.
2. Make sure to re-use the original packing material to ship the UPS.
®
Shutdown Software
7
Unpacking the UPS and Site Preparation