Environmental Conditions; Access To Area; Floor Loading; Inventory List - Liebert GXT3-240TBATTCE User Manual

Table of Contents

Advertisement

2.4

Environmental Conditions

Install the Liebert
turned off. Place it on a level, even surface in an area with unrestricted airflow around the unit. The
installation location must be free of water, flammable liquids, gases, corrosives and other conductive
contaminants. Maintain a minimum clearance of 100mm (4 inches) in the front and rear of the UPS.
Maintain an ambient temperature range of 0 to 40°C (32 -104°F).
See 8.0 - Specifications for acceptable environmental conditions.
2.5

Access to Area

The area where the Liebert GXT3-10000T220 is to be placed must have sufficient space for
installation procedures and for routine maintenance. The UPS is narrow enough to pass through
standard doorways.
2.6

Floor Loading

Ensure that the floor where the UPS will be installed will support the unit's weight (see Table 9 for
the unit's weight).
2.7

Inventory List

• CD containing:
• Liebert MultiLink
• Configuration Software
• User Manual
• Terminal Block Communication terminals
• Floor-mount brackets
• Warnings, safety instructions booklet and WEEE recycling sheet (ISO 14001 compliance)
• USB cable
• Hardwire terminal block cover plate and mounting screws
• Single input bypass jumper
• Battery cabinets contain one DC power cable
More user manuals on
®
GXT3
indoors in a controlled environment where it cannot be accidentally
NOTE
UPS operation in sustained temperatures outside the range of 15-25°C (59°-77°F) will reduce
battery life.
®