AC Input Indicator LED (Green)

The AC Input indicator LED is illuminated when utility power is available
and within the input specifications.

Output Voltage Selection

The Output Voltage is user configurable and is designed to allow select-
ing or changing the desired output voltage to match the utility via the
GXT 2U Configuration Program provided with the UPS. The settings to
choose from are 200, 208, 220, 230, and 240 VAC output. The factory
default setting is 208 VAC.
CAUTION
!
Never change the voltage settings while the UPS is ON and
powering connected loads.
NOTE
Setting output voltage to 200 VAC will cause the UPS unit to
be derated to 2400 VA, 1680 watts.