Troubleshooting Guide - Liebert 2700VA User Manual

Liebert power availability upstation user manual 2700va, 208v
Table of Contents

Advertisement

Under fault conditions, the Fault indicators will be illuminated indefinitely
while battery charger is operational, or for a maximum of 5 minutes while
battery charger is not operational.
If a problem persists, consult your local dealer, Liebert representative or
contact the Liebert Worldwide Support Group. Please have the UPS
model number and serial number available at the time of your inquiry.

Troubleshooting Guide

Problem
UPS fails to start
when the ON
button is pressed.
Battery indicator
LED is illuminated.
UPS has reduced
battery time.
Cause
UPS is short circuited or
overloaded.
UPS not plugged in.
UPS input protection fuse
has blown/opened.
Utility voltage out of UPS
input range.
Batteries are not fully
charged.
UPS is overloaded.
Batteries may not be able to
hold a full charge due to
age.
Ensure UPS is OFF.
Disconnect all loads and
ensure nothing is lodged in
output receptacles. Ensure
loads are not defective or
shorted internally.
UPS is operating from
battery mode, make certain
UPS is securely plugged
into the wall receptacle.
UPS is operating from
battery mode. Save data
and close applications.
Replace UPS input fuse,
then restart UPS.
UPS is operating from
battery mode. Save data
and close applications.
Ensure utility supply voltage
is within acceptable limits
for UPS.
Keep UPS plugged in
continuously at least 24
hours to recharge batteries.
Check load level display
and reduce the load on the
UPS.
Replace batteries. Contact
your local dealer, Liebert
representative or the Liebert
Worldwide Support Group
for replacement battery kit.
26
Solution