Troubleshooting Guide (Continued)
Problem
Fault and Bypass
indicator LEDs
and all load level
LEDs are
illuminated.
Fault and Bypass
indicator LEDs
and diagnostic
LED A are
illuminated.
Fault and Bypass
indicator LEDs
and diagnostic
LED B are
illuminated.
Fault and Bypass
indicator LEDs
and diagnostic
LED C are
illuminated.
Fault and Bypass
indicator LEDs
and diagnostic
LED D are
illuminated.
Fault and Bypass
indicator LEDs
and diagnostic
LED E are
illuminated.
Fault indicator
LED and
diagnostic LED A
and C are
illuminated.
Cause
UPS overloaded or load
equipment is faulty.
UPS internal fan has a
problem or UPS shutdown
due to temperature
condition. Load is on bypass
power.
UPS internal DC bus
overvoltage.
UPS control power supply
fault.
UPS PFC (Power Factor
Correction Circuit) fault.
UPS inverter fault.
UPS failed the battery test.
Check load level display
and remove non-essential
loads. Recalculate the load
and reduce number of loads
connected to UPS. Check
load equipment for faults.
Ensure UPS is not
overloaded, ventilation
openings not blocked, or
room ambient temperature
is not excessive. Wait 30
minutes to allow UPS to
cool, then restart UPS. If
UPS does not restart,
contact your local dealer,
Liebert representative or the
Liebert Worldwide Support
Group.
UPS requires service.
Contact your local dealer,
Liebert representative or the
Liebert Worldwide Support
Group.
UPS requires service.
Contact your local dealer,
Liebert representative or the
Liebert Worldwide Support
Group.
UPS requires service.
Contact your local dealer,
Liebert representative or the
Liebert Worldwide Support
Group.
UPS requires service.
Contact your local dealer,
Liebert Representative or
the Liebert Worldwide
Support Group.
Replace batteries. Contact
your local dealer, Liebert
representative or the Liebert
Worldwide Support Group.