Voltage Programming Button; Load Level Indicators-4 Green, 1 Amber; Battery Level Indicators-5 Green; Ac Input Indicator-Green - Liebert PowerSure PSI 1000 - 3000VA 60 Hz 120V User Manual

Liebert corporation user manual power supply 1000 - 3000va, 60 hz, 120v
Table of Contents

Advertisement

6.3

Voltage Programming Button

The PowerSure PSI contains a Voltage Programming button that allows the operator to select
the nominal utility voltage. This setting changes the utility transfer points (low and high) of
the UPS and the nominal output voltage when operating in Battery mode. The operator can
select between 110, 120 and 127 VAC output. The factory-default setting is 120 VAC.
The Voltage Programming button is a push button type and is behind the plastic bezel on
the front panel of the UPS. To access the button, the front bezel must be removed.
6.4
Load Level Indicators—4 green, 1 amber
The Load Level Indicators display the approximate electrical load placed upon the UPS.
The UPS Load Level Indicators are displayed in 25% increments as shown in Figure 12.
Figure 12 Load level indicators—4 green, 1 amber
Upon detection of an output overload condition, the amber overload (>100%) indicator flashes and an
audible alarm activates. If the UPS shuts down due to an overload condition, the amber overload
(>100%) indicator illuminates (see Troubleshooting section for details).
6.5
Battery Level Indicators—5 green
The Battery Level Indicators display the approximate battery capacity.
The approximate battery capacity is displayed when the UPS is operating in Normal, Buck/Boost, or
Battery mode.
The Battery Level Indicators are displayed in 20% increments as shown in Figure 13:
Figure 13 Battery level indicators—5 green
The PowerSure PSI is equipped with automatic and remote battery test features. The automatic test
occurs every 14 days if utility has not been interrupted; this option may be configured by the user.
Should the battery fail this test, the amber Battery Indicator will be illuminated and an alarm will
sound (see Troubleshooting section for details).
The remote test feature functions with MultiLink 3.x software and can remotely initiate the battery
test.
6.6
AC Input Indicator—Green
The AC Input Indicator illuminates when utility power is available and within the input specifica-
tions. This indicator flashes when the UPS detects a Site Wiring Fault (line-neutral reversal or neu-
tral not grounded properly) (see Troubleshooting section for details).
6.7
Buck/Boost Indicator—Green
The Buck/Boost Indicator illuminates when the UPS is operating in Boost mode to compensate for a
low utility voltage condition. This indicator flashes when the UPS is operating in Buck mode to com-
pensate for a high utility voltage condition (see Troubleshooting section for details).
6.8
Battery Indicator—Green/Amber
The Battery Indicator illuminates green when the UPS is operating on battery and flashes green
when a low battery condition occurs. The Battery Indicator illuminates amber when a bad battery is
detected, indicating that the batteries need to be replaced (see Troubleshooting section for details).
15
Controls and Indicators

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents