3

STANDARD OPERATING DATA

PK-FK INDOOR UNITS WITH PUG OUTDOOR UNITS
MODELS
Item
Voltage
Frequency
Total Input
Indoor Fan Current
Booster Heater Current
Outdoor Fan Current (FLA)
Compressor Current (230v)
Condensing Pressure
Suction Pressure
Discharge Temperature
Condensing Temperature
Suction Temperature
Refrigerant Pipe Length
Refrigerant Charge
Intake Air Temperature
Discharge Air Temperature
Fan Speed
Airflow (High)
Intake Air Temperature
Fan Speed
Airflow (High)
Capacity
SHF
4
Unit
V
Hz
kW
A
A
A
A
PSIG
PSIG
°F
°F
°F
FT.
-
DB
°F
WB
°F
DB
°F
WB
°F
RPM.
CFM
DB
°F
WB
°F
RPM.
CFM
BTU/H
--
PK18FK
PK24FK
Cooling
Cooling
208/230
208/230
60
60
1.82
2.38
0.8
0.8
--
--
0.5
0.5
7.3
9.6
260
271
85
86
182
191
107
112
62
58
25
25
3 lbs 8 oz
3 lbs 6 oz
80
80
67
67
60
58
59
57
1490
1490
710
710
95
95
--
--
1050
1050
1690
1785
19400
23400
0.77
0.71
PK30FK
PK36FK
Cooling
Cooling
208/230
208/230
60
60
2.85
3.34
0.9
1.0
--
--
0.5
1.4
12.6
14.0
287
278
84
77
196
191
109
112
61
59
25
25
4 lbs 3 oz
3 lbs 15 oz
80
80
67
67
58
58
56
56
1490
1490
990
990
95
95
--
--
1050
1100
1600
2340
29200
34200
0.69
0.65