Refrigerant System - Mitsubishi PUG18AYB Technical Manual

Mitsubishi pug18ayb; pug24ayb; pug30ayb; pug36ayb; pug42ayb split-type, air conditioners, pug outdoor unit
Table of Contents

Advertisement

12

REFRIGERANT SYSTEM

SERVICE PORTS
There are two service ports available to service technicians. One port is located at each of the two base valves.
A.
Liquid Line Base Valve Service Port. This port is used to evacuate the refrigerant line set when the ball valve is in
the closed position. It may also be used to measure the liquid line pressure or, more accurately, the "saturated line"
pressure during normal operation. During cooling operation this service port is downstream of the metering orifice
which is installed inside of the liquid line base valve body. While in the cooling mode this pressure is typically 25 to 40
PSI above that of the suction base valve pressure (usually 85 to 110 PSI).
B.
Suction Base Valve Service Port. This port is also used to evacuate the indoor unit and line set during installation.
The ball valve must be closed to evacuate the line set and indoor unit. During normal cooling mode operation this pres-
sure port indicates evaporator pressure (minus line set pressure drop). Typical cooling mode pressure readings here
are in the range of 55 to 80 PSI during summer operation.
C. Both refrigerant lines must be insulated because the "cooling side" metering device is located in the outdoor
unit. Failure to insulate the liquid line, or more accurately the "saturation line", will result in condensate dripping from
the line and poor cooling performance.
D. Metering Devices. A fixed orifice that is located in the liquid base valve meters refrigerant in the cooling mode. If a
restriction or a compressor failure occurs this orifice can be easily accessed and cleaned after refrigerant is recovered.
It is important to use a back-up wrench on the liquid line base valve connections when accessing the orifice. Failure to
do so could loosen the base valve connections and cause a refrigerant leak.
OUTDOOR
COIL
Mitsubishi Electronics 2003
COMPRESSOR
FIELD CONNECTION
LINE
036-21534-001 Rev. B (0703)
FIELD CONNECTION
INDOOR COIL
LINE
SUCTION
ACCUMULATOR
COOLING CYCLE FLOW
29

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Pug24aybPug30aybPug36aybPug42ayb

Table of Contents