Mitsubishi PUG18AYB Technical Manual page 27

Mitsubishi pug18ayb; pug24ayb; pug30ayb; pug36ayb; pug42ayb split-type, air conditioners, pug outdoor unit
Table of Contents

Advertisement

10
MICROPROCESSOR CONTROL
C. Low Ambient Temperature Switch (LATS). The purpose of this switch is to extend cooling operation in low outdoor
temperatures as low as 25°. The outdoor unit uses a high side pressure switch to cycle the fan. When pressure drops
to 165 PSI (+/-10), the switch opens and the fan stops. When pressure rises to 300 (+/- 10), the switch closes and the
fan restarts. A jumper is factory installed in place of the low ambient pressure switch. This jumper must be removed
when a low ambient accessory kit is installed.
During low ambient cooling operation the indoor unit may initiate an "air defrost" of the indoor coil once during every 16
minutes of continuous cooling operation. This insures that the coil has adequate airflow and should not be considered
as a fault.
D. Crankcase Heater (CCH) - A crankcase heater is installed into all PUG condensing units to protect the compressor
when operating under low ambient conditions. When line voltage is first applied to the outdoor unit, the control will
energize the crankcase heater. The control will continue to energize the CCH until the first call for compressor opera-
tion. The control never energizes the CCH during compressor operation. The control will energize the CCH thirty min-
utes after the compressor turns off. It will then cycle the CCH on for 30 minutes and off for 30 minutes repeatedly until
the compressor is again turned on.
E.
Compressor Contactor (CC) - The compressor contactor is energized with 24VAC when a 12 VDC is input to the out-
door unit on control wires 1 and 2 from the indoor unit. This 12 VDC signal is generated and sent from the indoor unit
on all calls for compressor operation.
F.
Outdoor Fan Motor (ODF) - The outdoor fan motor typically operates at the same time as the compressor. However,
the fan may be off while the compressor is operating during low ambient cooling conditions as described previously.
G.
Transformer Input (24VAC) - The secondary side of the transformer supplies 24 volts AC to the circuit board on the
"24VAC" terminals. This voltage operates the internal circuits of the board and also provides voltage to the compressor
contactor when appropriate. The primary side of the transformer is powered with line voltage from terminals marked
"L1" and "L2" on the board.
H. Line Voltage - Line voltage is input and output from the circuit board on the terminals marked "L1" and "L2". There are
four terminals marked "L1". These terminals provide "L1" input to the board and "L1" output to the transformer, crank-
case heater and the outdoor fan motor.
There are two terminals marked "L2". One terminal provides "L2" line voltage input to the board. The other provides
"L2" output to the transformer.
I.
Anti-Recycle Delay Timer - The control provides an "anti-recycle delay" of three minutes in the cooling mode.
J.
Time Shortening - Placing the defrost jumper to the "TEST" position shortens timings of the control to the following
values.
1. Anti-Recycle - 36 seconds
2. CCH Cycles - 24 seconds
3. Compressor Run - 1 second
4. Low Pressure Bypass - 12 seconds
K.
Last Fault Memory Recall. The control maintains a memory of the last fault that occurred. The last fault code can be
recalled by moving the defrost jumper to the "TEST" position and observing the "STATUS" LED display. The control
stores only the last fault code. The control will reset the fault code memory when the line voltage to the outdoor unit is
turned off.
L.
LED Function. The board has four LED's which provide the following function:
1. "STATUS" LED indicates normal operation or faults as follows:
LED FLASHES
Constant on LED
1 Flash Sequence
2 Flash Sequence
3 Flash Sequence
4 Flash Sequence
2.
"CCH" LED indicates that the crankcase heater is energized.
3.
"2" LED indicates that the indoor unit is calling for compressor operation, 12VDC is present on control wire #2.
Mitsubishi Electronics 2003
Off
Anti-recycle delay active. If the HPSS or LPS opens, the anti-recycle
INDICATION OF CONDITION
Normal Operation, no fault, no "call"
will activate for 3 minutes before the fault can be displayed.
Defrost Sensor Closed
High Pressure Safety Switch Open
LATS Open
Low Pressure Safety Switch Open
036-21534-001 Rev. B (0703)
27

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Pug24aybPug30aybPug36aybPug42ayb

Table of Contents