● 1st Stage Deadband
(1–6°F)
● 2nd Stage Deadband
● 2nd Stage Deadband
Number of degrees past 1st stage before 2nd stage turns
on. (0–10°F)
● 2nd Stage Timer
Number of minutes past 1st stage before 2nd stage turns
on. (0–60 mins.) (The 2nd stage deadband must also be
met)
● 2nd Stage Turnoff Point
Deadband or Setpoint.
● 3rd Stage Deadband
● 4th Stage Deadband
The 3rd and 4th stage deadband settings have the same
adjustable steps as 2nd stage deadband.
● Heat Pump Settings
Only available when dip switch is set for Heat Pump
operation. A local outdoor thermostat connected to the
thermostat is reqired.
● Heat Pump Lockout – DISABLED
● Heat Pump Lockout – ENABLED
Turns on Heat Pump Lockout.
● HP Lockout Outdoor Temp
Heat Pump will not run below this temp. (0°–75°F)
● Aux Heat Lockout – DISABLED
● Aux Heat Lockout – ENABLED
Turns on Aux Heat Lockout.
● Aux Heat Lockout Temp
Aux Heat will not run above this temp. (0°–75°F) GAS/EL
or HP dip switch must be set for HP and GAS or ELEC dip
switch must be set for ELEC.
www.DaikinApplied.com
h
igh
►
(2°)
For TSTATD4272CGT Models Only
● AUX Output Settings
►
Allows the W3/AUX output to be used for Heating,
Humidification, or Dehumidification.
►
(2°)
IMPORTANT: Aux Output Usage must be set for Hum or
Dehum before any settings will take effect in the Humidity
►
Main Menu.
(2 mins)
The AUX Output polarity may be set for Normally Open or
Normally Closed to accommodate different types of
►
humidification and dehumidification equipment.
(Deadband )
►
►
►
● Sensor Settings
►
When a remote sensor is connected to the thermostat, the
user may choose which sensor source is used to measure
room temperature.
• Thermostat sensor only
►
(65°)
• Wired Sensor only
• Average remote/thermostat
►
The wired sensor may be used as follows:
• Outdoor sensor
• Remote Sensor
►
(65°)
• Supply Sensor
• Return Sensor
The thermostat and wired sensor may be calibrated -7° to
+7°F. The integral humidity sensor may be calibrated -20%
to +20% RH.
55
r
T
s
esoluTion
ouCh
● AUX output usage
● AUX output polarity
● Control Sensor
● Wired Sensor Use
● Calibrate Sensors
IM 1227 • MODELS DC THERMOSTATS
D
T
Creen
igiTal
hermosTaT
►
►
(W3)
►
(NO)
►
►
(thermostat)
►
(remote)
►
(0°)