Heta SCAN-LINE 800 AQUA Operating Instructions Manual page 15

Approved for use in smoke control areas when burning dry wood logs or authorised fuels
Table of Contents

Advertisement

Scan-Line 800 Aqua is delivered from
Heta so that it can be fitted on an
existing system with matching circula-
ting pump and safety valve.
By connection you should make sure
that the stove is supplied minimum
140 litres of water per hour and that
the existing system has a safety valve
which opens by maximum 2.5 bar
overpressure.
The SYR valve (point 5) is an extra
safety device which opens by a tem-
perature over 95° in the boiler.
Connect cold water pressure on maxi-
mum 15° on the ½" water connection
(point 1) (make sure that your water
company supplies approx. 600 litres
per hour. This could be checked by
seeing if you can fill a 10 litres bucket
on 1 minute.).
Connect the 12 mm copper pipe for
(point 2) water for outlet to the existing
outlet so that you visually can see
if the extra safety device has been
activated.
NB!! The installation should always
be carried out in accordance with
valid standards and regulations by an
authorized electrician.
15
Installation and Operating Instructions for Heta SL800 Aqua stove Pevex1018/AH/ver1:Jan 2013

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents